Danfoss AK-SM 800A: unpatched CVE-2026-129713, CVSS 9.8
CISA flags CVE-2026-129713, an unauthenticated stack overflow in Danfoss AK-SM 800A refrigeration controllers (CVSS 9.8). No fix until 5.5.x — keep them off the internet.
CISA published ICSA-26-328-03 on November 24, warning of an unauthenticated, remotely exploitable flaw in Danfoss AK-SM 800A refrigeration controllers — the boxes food retailers use to run commercial refrigeration, HVAC and lighting. CVE-2026-129713 is a stack-based buffer overflow scored CVSS v3.1 9.8 (and v4.0 9.3). There is no patch yet. If you operate these controllers, the only control available today is to get them off any internet-reachable path.
What's affected
- Danfoss AK-SM 8xxA Series (the AK-SM 800A line — 820A, 850A, 880A), all versions up to and including 5.4.0, per CISA.
- The fix is slated for an upcoming 5.5.x release. Danfoss also plans to remove the option to disable "Strict Mode" in future firmware.
The flaw
CISA describes a stack-based buffer overflow (CWE-121) in an unauthenticated CGI handler. A remote attacker sends specially crafted HTTP/S POST requests — no credentials needed — to corrupt memory and restart the web server. CISA states that arbitrary code execution with the web server's privileges is "hypothetically potential." The issue was reported by Carlo Meijer of Midnight Blue.
Exploitation status
CISA says it has no reports of known public exploitation of CVE-2026-129713 specifically.
That sits next to a separate, uncomfortable data point. Bleeping Computer reports that Danfoss controllers were abused in attacks on European supermarkets this autumn — attackers remotely shut down cooling or raised temperatures — and that supplier Sabcobel attributed the October incidents in France to "the same vulnerability previously seen." Neither Danfoss nor CISA has confirmed that CVE-2026-129713 is the exact flaw used in those attacks, so treat the link as reported, not proven. Either way, the exposure is real and the remedy is the same.
Action checklist
- Inventory every AK-SM 8xxA controller and confirm firmware; treat anything ≤ 5.4.0 as vulnerable.
- Remove the controllers from the public internet — no public IPs, no port-forwarded web UI. This is the single highest-impact step.
- Put remote access behind an up-to-date VPN and segment the controllers off the business network, behind a firewall.
- Enable Strict Mode on every affected device and set strong, unique credentials for all accounts.
- Track the 5.5.x release via the Danfoss security advisories page (advisory DSA-2026-12-01) and schedule the upgrade the moment it ships.
Context
This is the second wave of attention on Danfoss AK-SM800A pre-auth flaws this year — Midnight Blue's research follows earlier 2025 fixes (CVE-2025-41450/41451/41452). Refrigeration and building-management controllers keep landing on CISA's ICS list because they ship web servers with internet exposure and long patch cycles. For food retailers, the business-continuity risk — spoiled stock from a remote temperature change — arrives well before any code-execution proof-of-concept does.